What does the Ontario Building Code say about fibre cement siding?
What does the Ontario Building Code say about fibre cement siding?
Fibre cement is named in the 2024 Ontario Building Code (O. Reg. 163/24) in two places: the scope article that sets out which cladding types the cladding section covers (9.27.1.1.), and the face-sealed article (9.27.3.6.). Beyond those two mentions, the Code contains no dedicated fibre cement subsection, no material standard, no minimum thickness, and no gap or clearance rule specific to fibre cement. Installation follows the general cladding articles plus the manufacturer's written instructions.
Here is what the general articles require for any cladding, including fibre cement.
- Two planes of protection: the cladding itself is the first plane; a drainage plane with sheathing membrane and flashing is the second (9.27.2.2.(4), 9.27.2.3., 9.27.3.1.).
- Sheathing membrane: at least one layer of CAN/CGSB-51.32-M breather-type membrane, joints lapped not less than 100 mm, upper sheets over lower where applied horizontally (9.27.3.3.). The membrane may be omitted under face-sealed fibre cement sheets where all edges land on framing and joints are sealed and battened or shiplapped (9.27.3.6.).
- Flashing: required at every horizontal junction between cladding elements and every horizontal offset; over wall openings where the vertical distance from the bottom of the eave to the top of the trim is more than one-quarter of the eave's horizontal overhang (9.27.3.7., 9.27.3.8.). Flashing extends not less than 50 mm up behind the membrane, slopes not less than 6% to the exterior, and has end dams not less than 25 mm high.
- Sealant: between siding and adjacent door and window frames or trim, and at vertical joints between different cladding materials unless lapped or flashed (9.27.4.). Sealant must be a non-hardening exterior type meeting ASTM C834, C920, C1184 or C1311.
- Fastening: cladding is fastened to framing, furring or blocking (9.27.5.1.). Panel or sheet cladding up to 7 mm thick uses 38 mm nails; over 7 mm, 51 mm nails, at 150 mm spacing along edges and 300 mm along intermediate supports (Table 9.27.5.4.-A). Fasteners must be corrosion-resistant and compatible with the cladding (9.27.5.5.), and penetrate not less than 25 mm into framing, the depth the Code sets for cladding other than shakes, shingles and vinyl (9.27.5.7.).
- Ground clearance: the Code's 200 mm clearance rule (9.27.2.4.) applies to cladding adversely affected by moisture, naming untreated wood, plywood, OSB, waferboard and hardboard as examples. Fibre cement is not named in that list. Ask the manufacturer's instructions what clearance they require.
Because the Code has no fibre cement subsection, the manufacturer's written instructions govern the details. Ask any contractor quoting this work to show you the manufacturer's installation guide and explain how the flashing, membrane and fastening details in that guide are reflected in their quote.
If you want to hear from Ottawa siding contractors directly, the request form on this page sends your project details to contractors listed in the Ottawa Construction Network directory.
Related service: Fibre Cement Siding What it costs: Fibre cement siding